Layout Example, Door Open (Option +B051) - ABB ACQ580-34 Hardware Manual

Drives for water
Hide thumbs Also See for ACQ580-34:
Table of Contents

Advertisement

40 Guidelines for planning the mechanical installation

Layout example, door open (option +B051)

2c
2a
13
A
4
2c
2a
5
6
L1/U1
L2/V1
3
L3/W1
10
13
PE
T3/W2
3
T2/V2
T1/U2
3
9
11
A
1
Supporting frame of the cabinet
2a
Vertical (2a) and horizontal (2b) air baffles that
separate the cool and hot areas (leakproof
entries). See section Preventing the recirculation
2b
of hot air.
2c
Optional air baffle that is needed when there is
no fan on the lower part of the cabinet door. See
section Preventing the recirculation of hot air.
3
Cabinet grounding busbar (PE)
4
Input power cable including the protective ground
conductor (PE) of the drive
5
Disconnector and fuses
6
Contactor
7
Drive module
14
B
15
1
2b
7
8
12
A – A
B
16
B– B
8
LCL filter module
9
Motor cable including the protective ground con-
ductor of the drive module
10
Drive module control unit.
Note: The upper door air inlet is critical for proper
cooling of the control unit.
11
External control cables
12
Grounding screws
13
Alternative to grounding screws (12)
14
Air flow to the roof
15
Air flow through the drive module
16
Air flow through the LCL filter

Advertisement

Table of Contents
loading

Table of Contents