Advertisement

Power supply connection example
1)
1)
External power supply, 24 V AC/DC
WARNING!
Do not connect the +24 V AC cable to the control unit ground when the control
unit is powered using an external 24 V AC supply.

Start-up

Setting the parameters

1. Power up the drive.
2. If no warning is shown,
make sure that the values of both parameters 15.02 and 15.01 are CMOD-02.
If warning A7AB Extension I/O configuration failure is shown,
make sure that the value of parameter 15.02 is CMOD-02.
set the parameter 15.01 value to CMOD-02.
You can now see the parameters of the extension module in parameter group 15 I/O
extension module.

Diagnostics

Faults and warning messages

Warning A7AB Extension I/O configuration failure.

LEDs

The extension module has one diagnostic LED.
Color
Green

Technical data

Dimension drawing:
The dimensions are in millimeters and [inches].
+
24V AC/DC + in
40
24V AC/DC - in
-
41
Description
The extension module is powered up.
Optional I/O extension modules 171
CMOD-02