Losses, cooling data and noise

The air flow direction is from bottom to top.
This table shows typical heat loss values, required air flow and noise at the nominal ratings
of the drive. The heat loss values can vary depending on voltage, cable conditions, motor
efficiency and power factor. To obtain more accurate values for given conditions, use ABB
DriveSize tool (http://new.abb.com/drives/software-tools/drivesize).
Drive type
Frame size
ACQ580-34-
U
= 400 V, IEC
N
246A-4
R11
293A-4
R11
365A-4
R11
442A-4
R11
505A-4
R11
585A-4
R11
650A-4
R11
U
= 480 V, IEC
N
246A-4
R11
293A-4
R11
365A-4
R11
442A-4
R11
505A-4
R11
585A-4
R11
650A-4
R11
U
= 480 V, UL (NEC)
N
240A-4
R11
302A-4
R11
361A-4
R11
414A-4
R11
477A-4
R11
The cooling air temperature rises 30 degrees Celsius when it goes through the drive module
if the temperature of the input cooling air is 40 degrees Celsius and the drive is operating
with nominal load.
Air flow
3
3
m
/h
ft
/min
2100
1279
2100
1279
2100
1279
2100
1279
2100
1279
2100
1279
2100
1279
2100
1279
2100
1279
2100
1279
2100
1279
2100
1279
2100
1279
2100
1279
2100
1279
2100
1279
2100
1279
2100
1279
2100
1279
Technical data 115
Heat dissipation
W
5280
6400
8000
10000
10000
12600
14200
5220
5220
7830
9135
9135
9135
10440
5280
6525
7830
9135
10440
3AXD00000586715
Noise
dB(A)
72
72
72
72
72
72
72
72
72
72
72
72
72
72
72
72
72
72
72