Cabling The Factory-Integrated-In-Rack Option: Process Overview; Guidelines For Cabling - HPE 3PAR StoreServ 9000 Customer Self Install Manual

Hide thumbs Also See for 3PAR StoreServ 9000:
Table of Contents

Advertisement

Cabling the factory-integrated-in-rack option:
Process overview
IMPORTANT: Do not turn on power to the components at this time. Connect the power cables and
keep the power off until you power on the components.
IMPORTANT: To enable access to components for servicing, neatly route and secure the cables
along the sides of the rack.
For an HPE 3PAR StoreServ 9000 Storage system that is factory integrated in an HPE rack, the internal
cabling for the data cables and power cables has been completed before shipment; however, you must
complete the following additional cabling process:
Procedure
1. Review Guidelines for cabling on page 24.
2. Review Guidelines for redundant power cabling on page 26.
3. Complete Cabling the physical service processor (if installed) on page 27.
4. Complete Cabling the controller nodes: Process overview on page 28.
5. Complete Cabling the power cords of the power distribution units to the power receptacles at
the operating site on page 32.
6. Review Powering on: Process overview on page 33 and complete the process.

Guidelines for cabling

Guidelines for the minimum bend radius of the cable
Bend radius is defined as the minimum radius to which the cable may safely be bent during installation
without the risk of permanent damage resulting in excessive attenuation or even breakage.
Use the manufacturer guidelines for the minimum bend radius of a cable. If manufacturer guidelines have
not been provided, use the general guidelines provided in the following table.
CAUTION: Bending optical cables tightly can damage the internal fibers, causing signal loss,
reduced reliability, and performance problems.
IMPORTANT: Minimum bend radius is not the same as minimum bend diameter.
Table 3: General minimum bend radius by cable type
Cable type
Standard power cable
Active optical cable (AOC)
Fiber optical cable
24

Cabling the factory-integrated-in-rack option: Process overview

Minimum bend radius
1 in (2.5 cm)
2 in (5.08 cm)
1.75 in (4.44 cm)
Table Continued