5 General Specifications

Line power supply (L1, L2, L3):
Supply voltage
Supply voltage
Supply frequency
Max. imbalance temporary between line phases
True Power Factor (λ)
Displacement Power Factor (cos ϕ) near unity
Switching on input supply L1, L2, L3 (power-ups)
Environment according to EN60664-1
The unit is suitable for use on a circuit capable of delivering not more than 100.000 RMS symmetrical Amperes, 500/600/690 V maximum.
Motor output (U, V, W):
Output voltage
Output frequency
Switching on output
Ramp times
* Voltage and power dependent
Torque characteristics:
Starting torque (Constant torque)
Starting torque
Overload torque (Constant torque)
Starting torque (Variable torque)
Overload torque (Variable torque)
*Percentage relates to the nominal torque.
Digital inputs:
Programmable digital inputs
Terminal number
Logic
Voltage level
Voltage level, logic'0' PNP
Voltage level, logic'1' PNP
Voltage level, logic '0' NPN
2)
Voltage level, logic '1' NPN
2)
Maximum voltage on input
Pulse frequency ranges
(Duty cycle) Min. pulse width
Input resistance, R
i
MG.33.U2.22 - VLT
®
is a registered Danfoss trademark
5 General Specifications
FC 302: 380-500 V ±10%
FC 302: 525-690 V ±10%
50/60 Hz
3.0% of rated supply voltage
≥ 0.9 nominal at rated load
(> 0.98)
maximum 1 time/ 2 min.
overvoltage category III/pollution degree 2
0–100% of supply voltage
0–800* Hz
Unlimited
0.01-3600 sec.
maximum 160% for 60 sec.
maximum 180% up to 0.5 sec.
maximum 160% for 60 sec.
maximum 110% for 60 sec.
maximum 110% for 60 sec.
18, 19, 27
1)
, 29, 32, 33,
PNP or NPN
0-24 V DC
< 5 V DC
> 10 V DC
> 19 V DC
< 14 V DC
28 V DC
0-110 kHz
approximately 4 kΩ
5
*
*
*
*
4 (6)
4.5 ms
5-1