Instruction Manual High Power
EMC standards, Immunity
See section on special conditions in the Design Guide
Protection and Features:
Electronic thermal motor protection against overload.
Temperature monitoring of the heatsink ensures that the adjustable frequency drive trips if the temperature reaches a predefined level. An
overload temperature cannot be reset until the temperature of the heatsink is below the values stated in the tables on the following pages
(Guideline - these temperatures may vary for different power sizes, enclosures, etc.).
The adjustable frequency drive is protected against short-circuits on motor terminals U, V, W.
If a line phase is missing, the adjustable frequency drive trips or issues a warning (depending on the load).
Monitoring of the intermediate circuit voltage ensures that the adjustable frequency drive trips if the intermediate circuit voltage is too low or
too high.
The adjustable frequency drive constantly checks for critical internal temperature levels, load current, high voltage on the intermediate circuit
and low motor speeds. As a response to a critical level, the adjustable frequency drive can adjust the switching frequency and/ or change the
switching pattern in order to ensure the performance of the drive.
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
MG.33.U2.22 - VLT
®
is a registered Danfoss trademark
5 General Specifications
EN 61800-3, EN 61000-6-1/2,
5
5-5