Danfoss VLT Automation Drive FC 300 Instruction Manual page 121

High power
Hide thumbs Also See for VLT Automation Drive FC 300:
Table of Contents

Advertisement

VLT
®
Automation Drive FC 300
Instruction Manual High Power
Line Power Supply 3 x 525-690 V AC
FC 302
High/ Normal Load*
Typical shaft output at 550 V
[kW]
Typical shaft output at 575 V
[HP]
Typical shaft output at 690 V
[kW]
Enclosure IP21
Enclosure IP54
Enclosure IP00
Output current
Continuous
(at 550 V) [A]
Intermittent (60 sec overload)
(at 550 V) [A]
Continuous
(at 575/690 V) [A]
Intermittent (60 sec overload)
(at 575/690 V) [A]
Continuous KVA
(at 550 V) [KVA]
Continuous KVA
(at 575 V) [KVA]
Continuous KVA
(at 690 V) [KVA]
Max. input current
Continuous
(at 550 V) [A]
Continuous
(at 575 V) [A]
Continuous
(at 690 V) [A]
Max. cable size, line power,
motor and load share [mm
(AWG)]
Max. cable size, brake [mm
(AWG)]
Max. external pre-fuses [A]
Estimated power loss
at rated max. load [W]
Weight,
enclosureIP21, IP 54 [kg]
Weight,
enclosureIP00 [kg]
Efficiency
Output frequency
Heatsink overtemp. trip
Power card ambient trip
* High overload = 160% torque during 60 s, Normal overload = 110% torque during 60 s
P250
HO
200
300
250
303
455
290
435
289
289
347
299
286
296
2 x 185
2
(2 x 350 mcm)
2
2 x 185
(2 x 350 mcm)
1
500
4875
4)
151
138
4)
0-600 Hz
230°F [110°C]
140°F [60°C]
MG.33.U2.22 - VLT
®
is a registered Danfoss trademark
P315
NO
HO
NO
250
250
315
350
350
400
315
315
400
D2
D2
D2
D2
D4
D4
360
360
418
396
540
460
344
344
400
378
516
440
343
343
398
343
343
398
411
411
478
355
355
408
339
339
390
352
352
400
2 x 185
(2 x 350 mcm)
2 x 185
(2 x 350 mcm)
550
5821
5185
6149
165
151
0.98
0-500 Hz
230°F [110°C]
140°F [60°C]
5 General Specifications
P355
HO
NO
315
355
400
450
355
450
E1
E1
E2
395
470
593
517
5
380
450
570
495
376
448
378
448
454
538
381
453
366
434
366
434
4 x 240
(4 x 500 mcm)
2 x 185
(2 x 350 mcm)
700
5383
6449
263
221
0-500 Hz
185°F [85°C]
154°F [68°C]
5-11

Advertisement

Table of Contents
loading

Table of Contents