3.3 Mechanical Installation

Preparation of the mechanical installation of the adjustable frequency drive must be done carefully to ensure proper results and to avoid additional work
during installation. Start by taking a close look at the mechanical drawings at the end of this instruction manual to become familiar with the space demands.
3.3.1 Tools Needed
To perform the mechanical installation, the following tools are needed:
Drill with 0.39 or 0.47 in [10 or 12 mm] drill.
Tape measure
Wrench with relevant metric sockets (0.28-0.67 in (7-17 mm))
Extensions to wrench
Sheet metal punch for conduits or cable connectors in IP 21 and IP 54 units
Lifting bar to lift the unit (rod or tube max. Ø 1 inch (25 mm), able to lift minimum 880 lbs (400 kg)).
Crane or other lifting aid to place the adjustable frequency drive in position
A Torx T50 tool is needed to install the E1 enclosure in IP21 and IP54 enclosure types.
3.3.2 General Considerations
Space
Ensure proper space above and below the adjustable frequency drive to allow airflow and cable access. In addition, space in front of the unit must be
allowed to be able to open the panel door.
Figure 3.8: Space in front of IP21/IP54 enclosure type D1 and D2.
NOTE!
Airflow direction, see
Wire access
Ensure that proper cable access is present including the necessary bending allowance. Since the IP00 enclosure is open, the bottom cables must be
attached to the back panel of the enclosure where the adjustable frequency drive is mounted, i.e., by using cable clamps.