5 General Specifications
Line Power Supply 3 x 525-690 V AC
FC 302
High/ Normal Load*
5
Max. input current
* High overload = 160% torque during 60 s, Normal overload = 110% torque during 60 s
5-12
Typical shaft output at 550 V
[kW]
Typical shaft output at 575 V
[HP]
Typical shaft output at 690 V
[kW]
Enclosure IP21
Enclosure IP54
Enclosure IP00
Output current
Continuous
(at 550 V) [A]
Intermittent (60 sec overload)
(at 550 V) [A]
Continuous
(at 575/690 V) [A]
Intermittent (60 sec overload)
(at 575/690 V) [A]
Continuous KVA
(at 550 V) [KVA]
Continuous KVA
(at 575 V) [KVA]
Continuous KVA
(at 690 V) [KVA]
Continuous
(at 550 V) [A]
Continuous
(at 575 V) [A]
Continuous
(at 690 V) [A]
Max. cable size, line power,
motor and load share [mm
2
(AWG)]
2
Max. cable size, brake [mm
(AWG)]
Max. external pre-fuses [A]
1
Estimated power loss
4)
at rated max. load [W]
Weight,
enclosureIP21, IP 54 [kg]
Weight,
enclosureIP00 [kg]
Efficiency
4)
Output frequency
Heatsink overtemp. trip
Power card ambient trip
MG.33.U2.22 - VLT
P400
HO
NO
HO
315
400
400
400
500
500
400
500
500
E1
E1
E2
429
523
523
644
575
785
410
500
500
615
550
750
409
498
498
408
498
498
490
598
598
413
504
504
395
482
482
395
482
482
4x240 (4x500 mcm)
4x240 (4x500 mcm)
2 x 185
2 x 185
(2 x 350 mcm)
(2 x 350 mcm)
700
5818
7249
7671
263
221
0.98
0-500 Hz
185°F [85°C]
154°F [68°C]
®
is a registered Danfoss trademark
VLT
®
Automation Drive FC 300
Instruction Manual High Power
P500
P560
NO
HO
NO
450
450
500
600
600
650
560
560
630
E1
E1
E1
E1
E2
E2
596
596
630
656
894
693
570
570
630
627
855
693
568
568
600
568
568
627
681
681
753
574
574
607
549
549
607
549
549
607
4x240 (4x500 mcm)
2 x 185
(2 x 350 mcm)
900
900
8727
8715
9673
272
313
236
277
Need help?
Do you have a question about the VLT Automation Drive FC 300 and is the answer not in the manual?
Questions and answers