Pre-Operation Instructions
1.
Pre-Operation Instructions
1.1
General
The FR-A800 or FR-F800 series from Mitsubishi Electric (ME), are families of frequency inverters.
The communication modules, option boards, enabling communication on different industrial
networks, are developed and produced by HMS Industrial Networks.
Examples of applications for the frequency inverters are:
•
Lifting equipment
•
Warehouse systems
•
Extruders
•
Centrifuges
1.2
Product Overview
The A8NDPV1 PROFIBUS Option Board allows information to be transferred seamlessly between
an FR-A800 or FR-F800 series inverter and a PROFIBUS network with minimal configuration re-
quirements. The interface installs directly onto the inverter's control board, and presents a stand-
ard DSUB port for connection to the PROFIBUS network.
The option board is connected directly to the control board of the inverter and communicates
with the inverter via a built-in communication port. Note that when the inverter's network com-
munication port is used by the A8NDPV1 PROFIBUS Option Board, it is unavailable for use by any
other network.
Before using the option board, please familiarize yourself with the product and be sure to thor-
oughly read the instructions and precautions contained in this manual. In addition, please make
sure that this instruction manual is delivered to the end user of the product, and keep this instruc-
tion manual in a safe place for future reference or unit inspection.
1.3
Features
•
PROFIBUS DPV1 communication according to IEC 61158 Type 3
•
Drive operation according to PROFIdrive V4.1 [PDTS]
– Supports Application class 1 functionality
•
Diagnostic support
•
Automatic baud rate detection
•
Baud rates up to 12 Mbit supported
•
Support for Set Slave Address (SSA) functionality, i.e. node address can be set from the net-
work by a configuration tool or by a PROFIBUS master
•
Customized GSD-file provided
•
Up to 64 bytes of I/O data in each direction
A8NDPV1 PROFIBUS Option Board
General
5
Need help?
Do you have a question about the A8NDPV1 and is the answer not in the manual?