9.2
Intervals for the detector overhaul at factory
Siemens Building Technologies
Fire & Security Products
Fire control
Check activation up to and including interface.
installations
Check customer system shutdown operations (work charged
to the customer or carried out by the customer himself). Fix a
time schedule with the customer.
Emergency
Activate ALARM with reset button depressed:
operation
–
Collective lines with test probe (1 line per collective mod-
function
ule).
Addressable lines with 1 detector per line.
–
Check activation of remote transmission.
Verify indicators on emergency operation FT.
Alarm organi-
Check the functioning of the delay times V1 and V2.
zation
Check of the delay time at mains failure.
Alarm activation by automatic fire detector set to ABSENT =
ALARM II.
Alarm activation by manual call point set to PRESENT and
ABSENT = ALARM II.
Verify the automatic switchover PRESENT / ABSENT using
event memory entry.
Check activation of remote transmission equipment with
ALARM II.
Check WARNING level by activation of a zone via FT.
Alarm equip-
In emergency power operation mode, check all alarm devices
ment
according to status level:
–
WARNING
ALARM I
–
ALARM II
–
–
REMOTE ALARM
FAULT
–
Check the activation periods (if programmed) for PRESENT
an ABSENT modes.
Check the remote transmission equipment according to in-
structions provided by the remote transmission equipment
supplier.
Heavy-duty applications in industrial areas (chemical processes, conveyor belts
for raw material etc.) were not taken into consideration in the standard values
below. The values have to be adapted accordingly.
HI62x will not be overhauled at the factory.
All detectors must be activated during "Detector test mode" after detector over-
haul.
Application range
Addressable Synova™
Clean
600 detectors
Moderate soiling
Collective Synova™
Clean
600 detectors
Moderate soiling
Definitions:
Application range "Clean", e.g.:
EDP rooms
–
Offices
–
Theatre, museum, churches, hotel guest rooms
–
Meeting halls, exhibition halls
–
Department stores, shopping halls
–
Hospitals
–
Application range "Moderate soiling", e.g.:
Storage and stock rooms, warehouses
–
Production halls and assembly areas
–
Cable ducts, risers, elevated floors
–
Wood industry, textile industry
–
High risk, e.g.:
Rooms and areas with high value concentration or sensitive work processes.
–
System performance check
Interval in years
Risk
Interval in years
Standard
High
Standard
High
Standard
High
Standard
High
007833_a_en_--.doc
6
5
5
4
5
4
3
2
17
03.2004