Technical Data - Beckhoff TwinSAFE EL6910 Operation Manual

Logic terminal
Hide thumbs Also See for TwinSAFE EL6910:
Table of Contents

Advertisement

3.3

Technical data

Product designation
Number of inputs
Number of outputs
Status display
Minimum/maximum cycle time
Fault response time
Watchdog time
Input process image
Output process image
Supply voltage (SELV/PELV)
Current consumption via E-bus
Power dissipation of the terminal
Dimensions (W x H x D)
Weight
Permissible ambient temperature (operation)
Permissible ambient temperature (transport/storage)
Permissible air humidity
Permissible air pressure (operation/storage/transport)
Climate category according to EN 60721-3-3
Permissible level of contamination according to EN 60664-1
Inadmissible operating conditions
Vibration / shock resistance
EMC immunity / emission
Shocks
Protection class
Permitted operating environment
correct installation position
Approvals
EL6910
EL6910
0
0
4 diagnostic LEDs
approx. 1 ms / according the project size
≤ watchdog times
min. 2 ms, max. 60000 ms
Dynamic, according to the TwinSAFE configuration in TwinCAT 3
Dynamic, according to the TwinSAFE configuration in TwinCAT 3
24 V
(–15% / +20%)
DC
approx. 160 mA
typically 1 W
12 mm x 100 mm x 68 mm
approx. 50 g
-25°C to +55°C (see notes in section Sample configuration for
temperature measurement [} 20])
-40 °C to +70 °C
5% to 95%, non-condensing
750 hPa to 1100 hPa
(this corresponds to an altitude of approx. -690 m to 2450 m above
sea level, assuming an international standard atmosphere)
3K3
(the deviation from 3K3 is possible only with optimal environmental
conditions and also applies only to the technical data which are
specified differently in this documentation)
Contamination level 2 (note chapter Maintenance [} 130])
TwinSAFE Terminals must not be used under the following operat-
ing conditions:
• under the influence of ionizing radiation (exceeding the
natural background radiation)
• in corrosive environments
• in an environment that leads to unacceptable soiling of the
Bus Terminal
conforms to EN 60068-2-6 / EN 60068-2-27
conforms to EN 61000-6-2 / EN 61000-6-4
15 g with pulse duration 11 ms in all three axes
IP20
In the control cabinet or terminal box, with minimum protection
class IP54 according to IEC 60529
see chapter Installation position and minimum distances [} 19]
CE, cULus, TÜV SÜD