Backup/Restore - Beckhoff TwinSAFE EL6910 Operation Manual

Logic terminal
Hide thumbs Also See for TwinSAFE EL6910:
Table of Contents

Advertisement

Access Rights
Change Password
Download Safe Logic Data
Download Mapping Data
Download Safe User Data /
Replacement Values
Download Info Data
Download Project Data in
Restore Mode
Activate / Deactivate Groups
4.8

Backup/Restore

Following the exchange of an EL6910, EJ6910 or EK1960, the previous project can be loaded to the new
device using the Backup/Restore mechanism.
In order to be able to use this functionality, the Backup/Restore mechanism must be enabled in the safety
project, and the terminals must be selected, on which the current CRC of the safety project is to be stored.
For a restore operation the user can specify the minimum number of selected terminals on which the correct
CRC must be stored.
Using the checkbox Restore User Administration the user can specify whether the user administration should
be transferred to the new device via the restore mechanism.
Fig. 128: Backup/Restore
In order to be able to use the Backup/Restore mechanism, create a backup of the current safety project and
store it on the hard disk of the controller, for sample. To carry out a restore, the user can either check when
starting the controller whether the serial number of the EL6910, EJ6910 or EK1960 has changed, or start the
restore manually via a service menu, e.g. in the visualization. Detailed information about the Backup/Restore
mechanism is available from Beckhoff Support.
EL6910
Description
Users can change their password.
The user can load the safety-related program onto the EL6910, EJ6910 or
EK1960.
The user can load the mapping data for inputs, outputs, FBs etc. onto the
EL6910, EJ6910 or EK1960.
The user can change safe user parameters on the EL6910, EJ6910 or
EK1960 and also change and load safe substitute values
The user can activate and load the info data for connections and FBs on
the EL6910, EJ6910 or EK1960.
The user can perform a restore. Not currently supported.
The user can execute Customizing (enable and disable TwinSAFE groups)
on the EL6910, EJ6910 or EK1960.
Version: 1.8.0
Operation
97

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents