Fig. 159 Creating A Link To Twinsafe Sc Terminal; Fig. 160 Selecting A Free Crc - Beckhoff TwinSAFE EL6910 Operation Manual

Logic terminal
Hide thumbs Also See for TwinSAFE EL6910:
Table of Contents

Advertisement

Fig. 159: Creating a link to TwinSAFE SC terminal
The CRC to be used can be selected or a free CRC can be entered under the Connection tab of the alias
device.
Entry Mode
TwinSAFE SC CRC 1 master
TwinSAFE SC CRC 2 master
TwinSAFE SC CRC 3 master
TwinSAFE SC CRC 4 master
TwinSAFE SC CRC 5 master
TwinSAFE SC CRC 6 master
TwinSAFE SC CRC 7 master
TwinSAFE SC CRC 8 master
Fig. 160: Selecting a free CRC
These settings must match the settings in the CoE objects of the TwinSAFE SC component.
The TwinSAFE SC component initially makes all available process data available. The Safety Parameters
tab typically contains no parameters. The process data size and the process data themselves can be
selected under the Process Image tab.
EL6910
Used CRCs
0x17B0F
0x1571F
0x11F95
0x153F1
0x1F1D5
0x1663B
0x1B8CD
0x1E1BD
Version: 1.8.0
Operation
115

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents