Status Leds; Fig. 177 El6910 Status Leds - Beckhoff TwinSAFE EL6910 Operation Manual

Logic terminal
Hide thumbs Also See for TwinSAFE EL6910:
Table of Contents

Advertisement

Logic error codes of LED Diag 2 (if LED Diag 1 is lit)
Flashing
Description
Code
1
Function block error in one of the TwinSAFE groups
2
Communication error in one of the TwinSAFE groups
3
Error combination: Function block and communication
4
General error in one of the TwinSAFE groups
5
Error combination: General and function block
6
Error combination: General and communication
7
Error combination: General, function block and communication
Environment error codes of LED Diag 2 (if LED Diag 1 is off)
Flashing
Description
Code
1
Maximum supply voltage µC1 exceeded
2
Supply voltage µC1 below minimum value
3
Maximum supply voltage µC2 exceeded
4
Supply voltage µC2 below minimum value
5
Maximum internal temperature exceeded
6
Internal temperature below minimum value
7
Valid temperature difference between µC1 and µC2 exceeded
8
not used
9
not used
10
General error
4.18.1.2
Flash code display
LED
Display
flashing
flickering
4.18.2

Status LEDs

The LEDs State 1 to State 4 indicate the current status of the EL6910.
Fig. 177: EL6910 status LEDs
EL6910
Description
400 ms ON / 400 ms OFF
1 second pause between the flash codes
50 ms ON / 50 ms OFF
Version: 1.8.0
Operation
125

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents