Device Record - Emerson Fisher Fieldvue DVC6030f Instruction Manual

Digital valve controllers
Table of Contents

Advertisement

Device Record

(TB > Display > Device Record )
The following parameters are contained in the Device
Record menu of the transducer block.
D Temp Max
Temperature Maximum (TEMP_MAX [86.1]) shows
the maximum temperature the instrument has
experienced since installation.
D Temp Max Time
Temperature Maximum Time (TEMP_MAX_TIME
[86.2]) shows the date and time when the Temp Max
occurred.
D Temp Min
Temperature Minimum (TEMP_MIN [86.3]) shows the
minimum temperature the instrument has experienced
since installation.
D Temp Min Time
Temperature Minimum Time (TEMP_MIN_TIME
[86.4]) shows the date and time when the Temp Min
occurred.
D Supp Press Max
Supply Pressure Maximum (SUPPLY_PRESS_MAX
[86.5]) shows the maximum supply pressure the
instrument has experienced since installation.
D Supp Press Max Time
Supply Pressure Maximum Time
(SUPP_PRESS_MAX_TIME [86.6]) shows the date
and time when the Supp Press Max occurred.
D Supp Press Min
Supply Pressure Minimum (SUPP_PRESS_MIN
[86.7]) shows the minimum supply pressure the
instrument has experienced since installation.
March 2006
Viewing Device Information
D Supp Press Min Time
Supply Pressure Minimum Time
(SUPP_PRESS_MIN_TIME [86.8]) shows the date
and time when the Supp Press Min occurred.
Block Errors
Table 7-2 lists conditions reported in the BLOCK_ERR
[6] and XD_ERROR [11] parameters. Conditions in
italics are not applicable for the transducer block and
are provided only for your reference.
Table 7-2. Transducer Block BLOCK_ERR and
XD_ERROR Conditions
Condition
Condition Name and Description
Number
0
Other - (N/A)
Block Configuration Error - Indicates that one of the
1
following parameters have been configured out of the
proper range: 15, 16, 47.1, 47.2, 46.3, 46.5, 42.7, 42.8.
2
Link Configuration Error - (N/A)
Simulate Active - Indicates that the simulation jumper is
in place on the aux terminals. This is not an indication
3
that the I/O blocks are using simulation data. See AO
block paramter SIMULATE [10] and DO block parameter
SIMULATE_D [10].
4
Local Override - (N/A)
5
Device Fault State − (NA)
6
Maintenance Needed Soon - (N/A)
7
Input failure/process variable has Bad status - (N/A)
8
Output failure - (N/A)
9
Memory failure - (N/A)
Lost Static Data - Indicates that manufacturing functional
10
or thermal tests were incomplete
11
Lost NV Data - (N/A)
12
Readback Check Failed - (N/A)
Device Needs Maintenance Now - Indicates that
13
manufacturing functional or thermal tests were incomplete
14
Power Up - (N/A)
15
Out of Service - Indicates Out of Service Mode.
7
7-7

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents