Emerson Fisher Fieldvue DVC6030f Instruction Manual page 276

Digital valve controllers
Table of Contents

Advertisement

DVC6000f Series
PlantWeb Alert
Alert Category
and (Group)
and (Default)
Drive Current
User Config.
(Electronics)
(Failed)
Drive Signal
User Config.
(Electronics)
(Maintenance)
Processor
User Config.
Impaired
(Maintenance)
(Electronics)
Output Block
User Config.
Timeout
(Maintenance)
(Configuration)
9
Blocks Set to
User Config.
Default
(Failed)
(Configuration)
Shutdown Alert
User Config.
(Configuration)
(Failed)
9-4
Table 9-1. Setting PlantWeb Alerts
Alert Condition
What the Alert is
and (Default)
Detecting
The difference between the
Drive Current
expected Drive Current and
(Enabled)
the actual Drive Current has
exceeded the configured limit.
The Drive Signal is greater or
Drive Signal
less than the expected
(Enabled)
maximum or minimum.
Program Memory
A failure in the Flash Memory
(Enabled)
where the program is stored.
A failure of the FRAM memory
Static Memory
where static parameters are
(Enabled)
stored.
Processor
A failure of the main
(Enabled)
Processor.
I/O Processor
A failure of the I/O Processor.
(Enabled)
If the analog or discrete output
Output Block
block has not executed or has
Timeout
remained out of service for
(Disabled)
longer than the configure
timeout, this alert is detected.
If the user has restarted with
defaults, all blocks have been
Blocks Set to Default
(Enabled)
restored to original factory
settings.
A user configured Self Test
Shutdown condition has taken
N/A
the instrument to OOS.
−Continued−
Related Parameters and
Guidelines for Setting
(Default)
Self Test Shutdown (No)
Shutdown Recovery (Auto)
Use default settings
Alert Point (50%)
Alert Time (5 sec)
Use default setting
Self Test Shutdown (No)
Use default settings
Shutdown Recovery (Auto)
Self Test Shutdown (No)
Use default settings
Shutdown Recovery (Auto)
Self Test Shutdown (No)
Use default settings
Shutdown Recovery (Auto)
Self Test Shutdown (No)
Use default settings
Shutdown Recovery (Auto)
Enable this alert for loops
where the execution is
critical. If the AO or DO
block is not scheduled, or
scheduled incorrectly, it will
trigger an alert after the
Timeout Alert Point has been
exceeded. Set the Timeout
Alert Point to a value
between
a. 30 seconds and
Timeout Alert Point (600 s)
b. the maximum time
Self Test Shutdown (No)
before a user should be
Shutdown Recovery (Auto)
notified. The minimum
number depends on the time
it takes for a host to
download a configuration to
the device.
Shutdown can be enabled if
it is desired to move the
valve to the Zero Power
Condition at the same time
that the alert is generated.
None
Use default settings
None
Use default settings
March 2006