Emerson Fisher Fieldvue DVC6030f Instruction Manual page 114

Digital valve controllers
Table of Contents

Advertisement

DVC6000f Series
Label
PARAMETER_NAME
Advise Alarm
ADVISE_ALM
UNACKNOWLEDGED
ALARM_STATE
TIME_STAMP
SUBCODE
VALUE
5
Failed Active
FAILED_ACTIVE
Maint Active
MAINT_ACTIVE
1. These parameters can be written when PWA_SIMULATE is active and Protect Category is not ALL.
5-48
Table 5-13. Transducer Block Parameter Definitions (Continued)
Index
RO /
Mode
Range
Number
RW
58
0=Undefined
58.1
RW
N/A
1=Acknowledged
2=Unacknowledged
0: Undefined
1: Clear−reported
58.2
RO
N/A
2: Clear−not reported
3: Active−reported
4: Active−not reported
58.3
RO
N/A
58.4
RO
N/A
58.5
RO
N/A
0: Drive Current
1: Drive Signal
2: Processor Impaired
3: Output Block Timeout
4: Blocks Set to Defaults
5: Travel Sensor
6: Outlet Pressure
Sensor
7: Supply Pressure
Sensor
8: Temperature Sensor
(1)
59
RO
N/A
9: Supply Pressure
10: Temperature Limit
11: Travel Deviation
12: Travel Limit
13: Travel Accumulator
14: Cycle Counter
15: Performance Critical
16: Performance
Reduced
17: Performance
Information
18: Shutdown Alert
0: Drive Current
1: Drive Signal
2: Processor Impaired
3: Output Block Timeout
4: Blocks Set to Defaults
5: Travel Sensor
6: Outlet Pressure
Sensor
7: Supply Pressure
Sensor
8: Temperature Sensor
(1)
60
RO
N/A
9: Supply Pressure
10: Temperature Limit
11: Travel Deviation
12: Travel Limit
13: Travel Accumulator
14: Cycle Counter
15: Performance Critical
16: Performance
Reduced
17: Performance
Information
18: Shutdown Alert
−Continued−
Protect
Initial Value
Category
Data Type: DS-71
Used to report alerts to host
system
0=Undefined
NONE
0=Undefined
N/A
0
N/A
0
N/A
Data Type: Float
Value of parameter at alarm time
0
N/A
for single alarm, 0 for multiple
alarms
Data Type: Bit String
0=inactive
All bits: 0
N/A
1=active
Failed Alert Status
Data Type: Bit String
0=inactive
All bits: 0
N/A
1=active
Maintenance Alert Status
Description