DVC6000f Series
Table 5-4. Parameters Affected by Restart with Defaults
Index
Parameter Name
Number
1
ST_REV
2
TAG_DESC
3
STRATEGY
4
ALERT_KEY
5
MODE_BLK
TARGET
PERMITTED
NORMAL
9
DD_RESOURCE
10
MANUFAC_ID
11
DEV_TYPE
12
DEV_REV
13
DD_REV
14
GRANT_DENY
15
HARD_TYPES
17
FEATURES
5
18
FEATURE_SEL
19
CYCLE_TYPE
20
CYCLE_SEL
21
MIN_CYCLE_T
22
MEMORY_SIZE
23
NV_CYCLE_T
26
SHED_RCAS
27
SHED_ROUT
28
FAULT_STATE
31
MAX_NOTIFY
32
LIM_NOTIFY
33
CONFIRM_TIME
34
WRITE_LOCK
37
ALARM_SUM
DISABLED
38
ACK_OPTION
39
WRITE_PRI
41
ITK_VER
42
DISTRIBUTOR
43
DEV_STRING
44
FB_OPTIONS
45
DIAG_OPTIONS
46
MISC_OPTION
47
SOFTWARE_REVISION
48
HARDWARE_REV
49
ELECTRONICS_SN
50
FACTORY_SN
51
FIELD_SN
52
DETAILED_STATUS
54
DEVICE_ID
55
STBY_SOFTWARE_REV
1
ST_REV
2
TAG_DESC
3
STRATEGY
4
ALERT_KEY
5
MODE_BLK
TARGET
PERMITTED
NORMAL
8
SP
9
OUT
11
PV_SCALE
EU 100%
EU 0%
Engineering Units
Decimal Places
5-8
Initial Value
Resource Block
0
spaces
0
0
Auto
Auto or Out of Service
Auto
spaces
0x5100
4601
varies with release
varies with release
All bits: 0
All bits: 1 (active)
All bits: 1 (active)
Set by mfgr.
0:1
0:0
3200
0
5760000
640000
640000
1=Clear
3
MAX_NOTIFY
640000
1=Unlocked
All bits: 0
Disabled
0
depends on device revision
0x5100
read random number
All options enabled
depends on licensed options
enabled
depends on device revision
Factory set
Factory set
spaces
spaces
Device ID
depends on software revision
AO Block
0
spaces
0
0
Out of Service
OOS+MAN+AUTO+CAS+
CAS
Auto
Dynamic
Dynamic
100
0
%
2
−Continued−
Table 5-4. Parameters Affected by Restart with Defaults
(Continued)
Index
Parameter Name
Number
AO Block (continued)
12
XD_SCALE
EU 100%
EU 0%
Engineering Units
Decimal Places
14
IO_OPTS
15
STATUS_OPTS
17
CAS_IN
18
SP_RATE_DN
19
SP_RATE_UP
20
SP_HI_LIM
21
SP_LO_LIM
22
CHANNEL
23
FSTATE_TIME
24
FSTATE_VAL
26
RCAS_IN
Status
Value
27
SHED_OPT
PID Block Parameters
1
ST_REV
2
TAG_DESC
3
STRATEGY
4
ALERT_KEY
5
MODE_BLK
TARGET
PERMITTED
NORMAL
8
SP
9
OUT
10
PV_SCALE
EU 100%
EU 0%
Engineering Units
Decimal Places
11
OUT_SCALE
EU 100%
EU 0%
Engineering Units
Decimal Places
13
CONTROL_OPTS
14
STATUS_OPTS
15
IN
Status
Value
16
PV_FTIME
17
BYPASS
18
CAS_IN
Status
Value
19
SP_RATE_DN
20
SP_RATE_UP
21
SP_HI_LIM
−Continued−
Initial Value
100
0
%
2
All off
All off
BAD:
NC:
const
0
+INF
+INF
100
0
1=analog valve input
0
0
BAD:
NoComm:
NoVal:
const
0 Trk
All off
0
spaces
0
0
Out of Service
OOS+MAN+AUTO+CAS+
RCAS+ROUT
Auto
Dynamic
Dynamic
100
0
%
2
100
0
%
2
0: Bypass enable
All off
BAD:
NC:
const
0
0
0
BAD:
NC:
const
0
+INF
+INF