DVC6000 Digital Valve Controllers
the difference between the target pressure and the
actual pressure exceeds the Pressure Deviation Alert
Point for a period of time greater than the Pressure
Deviation Time.
Locked in Safety Alert—This alert is indicated if the
ODV unit is locked in the safety position.
D Alert Record
Alert Record has Entries—This alert indicates that
an alert has been saved to the alert record.
Alert Record Full—This alert indicates that the alert
record is full.
Viewing Instrument Status (2-2)
6
Note
Status is not available with instrument
level AC.
To view the instrument status, from the Service Tools
menu select Status. This menu item indicates the
status of the Operational items listed below. The
status of more than one operational item may be
indicated.
Instrument Time
Inst Time Invalid
Calibration and Diagnostics
Cal in Progress
Autocal in Progress
Diag in Progress
Diag Data Avail
Operational
Press Ctrl Active
Multi-Drop
Integrator
Integrator Sat Hi
Integrator Sat Lo
6-4

Device Record (2-3)

Note
Device Record is not available for
instrument level AC.
From the Online menu, select Service Tools, Device
Record. Follow the prompts on the Field
Communicator display to view the following
parameters:
D Maximum Recorded Temperature—shows the
maximum temperature the instrument has experienced
since installation.
D Mininum Recorded Temperature—shows the
minimum temperature the instrument has experienced
since installation.
D View Number of Days Powered Up—indicates
in hours or days the total elapsed time the instrument
has been powered up.
D Number of Power Ups—indicates how many
times the instrument has cycled power.
Stroking the Digital Valve Controller
Output (2-4)
Note
Stroke Valve is not available with
instrument level AC.
From the Online menu, select Service Tools,Stroke
Valve. Follow the prompts on the Field Communicator
display to select from the following:
D Done—Select this if you are done. All ramping is
stopped when DONE is selected.
D Ramp Open—Ramps the travel toward open at
the rate of 1.0% per second of the ranged travel.
D Ramp Closed—Ramps the travel toward closed
at the rate of 1.0% per second of the ranged travel.
D Ramp to Target—Ramps the travel to the
specified target at the rate of 1.0% per second of the
ranged travel.