Output Splitter Function Block Parameter List

D Read/Write Capability: RO − Read Only, RW − Read Write
D Mode: The block mode(s) required to write to the parameter
D Double indentation and shaded Index Number indicates sub-parameter
Label
PARAMETER_NAME
Static Revision
ST_REV
Tag Description
TAG_DESC
5
Strategy
STRATEGY
Alert Key
ALERT_KEY
Block Mode
MODE_BLK
TARGET
ACTUAL
PERMITTED
NORMAL
Block Error
BLOCK_ERR
Setpoint
SP
Output 1
OUT_1
Output 2
OUT_2
Output 1 Range
OUT_1_RANGE
5-120
Table 5-47. Output Splitter Function Block Parameter Definitions
Index
RO /
Block
Number
RW
Mode
1
RO
N/A
0 to 65535
2
RW
ALL
7 bit ASCII
3
RW
ALL
0 to 65535
4
RW
ALL
1 to 255
5
7:OOS
5.1
RW
3:AUTO
2:CAS
5.2
RO
5.3
RW
OOS+AUTO+CAS
5.4
RW
1: Block
Configuration Error
7: Input Failure/Bad
6
RO
N/A
PV Status
8: Output Failure
14: Power-up
15: Out-of-Service
7
PV_SCALE +/− 10%
MAN
OUT_SCALE
8
OOS
+/− 10%
MAN
OUT_SCALE
9
OOS
+/− 10%
EU at 100%
EU at 0 %
10
RO
Unit Index
Decimal Point
Initial
Range
Value
Data Type: Unsigned16
The revision level of the static data associated with the
0
function block. The revision value will be incremented
each time a static parameter value in the block is
changed.
Data Type: Octet String
Spaces
The user description of the intended application of the
block.
Data Type: Unsigned 16:
The strategy field can be used to identify grouping of
0
blocks. This data is not checked or processed by the
block.
Data Type: Unsigned8
0
The identification number of the plant unit. This information
may be used in the host for sorting alarms, etc.
OOS until
Data Type: DS-69
block
The actual, target, permitted, and normal modes of the
configured,
block.
then last
Target: The requested block mode
valid target
Actual: The current mode of the block
OOS
Permitted: Allowed modes for Target
Normal: Most common mode for Target
OOS AUTO
CAS
AUTO+CAS
Data Type: Bit String
0
Inactive
=
1
Active
=
Dynamic
This parameter reflects the error status associated with
the hardware or software components associated with a
block. It is a bit string, so that multiple errors may be
shown.
Data Type: DS-65
Analog setpoint of the block
Data Type: DS-65
The primary analog output value calculated as a result of
executing the function (the first output value and status).
Data Type: DS-65
The primary analog output value calculated as a result of
executing the function (the second output value and
status).
100
Data Type: DS-68
0
The high and low scale values, engineering units code,
%
and number of decimal places to be used in displaying the
2
OUT value, this parameter has no effect on this block.
−Continued−