Available Configurations
Type DVC6010f: Sliding stem applications
Type DVC6020f: Rotary and long-stroke
sliding-stem applications [over 102 mm (4-inch)
travel]
Type DVC6030f: Quarter-turn rotary applications
Remote-Mounted Instrument
DVC6005f: Base unit for 2-inch pipestand or wall
mounting
DVC6015: Feedback unit for sliding-stem
applications
DVC6025: Feedback unit for rotary or long-stroke
sliding-stem applications
DVC6035: Feedback unit for quarter-turn rotary
applications
DVC6000f Series digital valve controllers can be
mounted on Fisher and other manufacturers rotary
and sliding-stem actuators.
Function Block Suites
J Standard Control (throttling control)
Includes AO, PID, ISEL, OS, AI, MAI, DO, and four
DI function blocks
J Fieldbus Control (throttling control)
Contains the AO function block
J Fieldbus Logic [discrete on/off]
Includes DO, and four DI function blocks
Block Execution Times
AO Block: 25 ms
PID Block: 30 ms
ISEL Block: 25 ms
OS Block: 25 ms
Electrical Input
Voltage Level: 9 to 32 volts
Maximum Current: 18 mA
Reverse Polarity Protection: Unit is not polarity
sensitive
Termination: Bus must be properly terminated per
ISA SP50 guidelines
March 2006
Table 1-1. Specifications
(1)
AI Block: 25 ms
MAI BLock: 40 ms
DO Block: 25 ms
DI Block: 20 ms
−continued−
Digital Communication Protocol
F
fieldbus registered device
OUNDATION
Physical Layer Type(s):
121—Low−power signaling, bus−powered, Entity
Model I.S.
511—Low−power signaling, bus−powered, FISCO
I.S.
(2)
Output Signal
Pneumatic signal as required by the actuator, up to
full supply pressure.
Minimum Span: 0.4 bar (6 psig)
Maximum Span: 9.5 bar (140 psig)
Action: Double, Single direct, and Single reverse
(2,6)
Supply Pressure
Recommended: 0.3 bar (5 psi) higher than
maximum actuator requirements, up to maximum
supply pressure
Maximum: 10 bar (145 psig) or maximum pressure
rating of the actuator, whichever is lower
Steady-State Air Consumption
Standard Relay: At 1.4 bar (20 psig) supply
pressure: Less than 0.38 normal m
At 5.5 bar (80 psig) supply pressure: Less than 1.3
3
normal m
/hr (49 scfh)
Low Bleed Relay: At 1.4 bar (20 psig) supply
pressure: Average value 0.056 normal m
(2.1 scfh)
At 5.5 bar (80 psig) supply pressure: Average value
3
0.184 normal m
/hr (6.9 scfh)
Maximum Output Capacity
At 1.4 bar (20 psig) supply pressure:
3
10.0 normal m
/hr (375 scfh)
At 5.5 bar (80 psig) supply pressure:
3
29.5 normal m
/hr (1100 scfh)
(2,5)
Independent Linearity
±0.5% of output span
Electromagnetic Interference (EMI)
Tested per IEC 61326-1 (Edition 1.1). Meets
emission levels for Class A equipment (industrial
locations) and Class B equipment (domestic
locations). Meets immunity requirements for
industrial locations (Table A.1 in the IEC
specification document). Immunity performance is
shown in table 1-2.
Introduction
(2,3,4)
3
/hr (14 scfh)
3
/hr
(3,4)
1-5
1
Need help?
Do you have a question about the Fisher Fieldvue DVC6030f and is the answer not in the manual?
Questions and answers