DVC6000f Series
Label
PARAMETER_NAME
INST_ALERTS_CONFIG2
Tvl Dev Alrt Pt
TVL_DEV_ALRT_PT
Tvl Dev Time
TVL_DEV_TIME
Tvl Dev DB
TVL_DEV_DB
Tvl Accum Alrt Pt
TVL_ACCUM_ALRT_PT
Tvl Accum DB
TVL_ACCUM_DB
Cycle Count Alrt Pt
CYCLE_COUNT_ALRT_PT
Cycle Count DB
5
CYCLE_COUNT_DB
Tvl Open Alrt Pt
TVL_OPEN_ALRT_PT
Tvl Open DB
TVL_OPEN_DB
Tvl Closed Alrt Pt
TVL_CLOSED_ALRT_PT
Tvl Closed DB
TVL_CLOSED_DB
Tvl Lo Lo Alrt Pt
TVL_LO_LO_ALRT_PT
Tvl Lo Lo DB
TVL_LO_LO_DB
Tvl Lo Alrt Pt
TVL_LO_ALRT_PT
Tvl Lo DB
TVL_LO_DB
Tvl Hi Alrt Pt
TVL_HI_ALRT_PT
Tvl Hi DB
TVL_HI_DB
Tvl Hi Hi Alrt Pt
TVL_HI_HI_ALRT_PT
Tvl Hi Hi DB
TVL_HI_HI_DB
5-56
Table 5-13. Transducer Block Parameter Definitions (Continued)
Index
RO /
Mode
Range
Number
RW
77
77.1
RW
ALL
> 0%, <= 125%
77.2
RW
ALL
> = 0, < = 120 seconds
77.3
RW
ALL
> = 0%, < = 100%
77.4
RW
ALL
> = 0
77.5
RW
ALL
0 − 100%
77.6
RW
ALL
> = 0
77.7
RW
ALL
0 − 100%
77.8
RW
ALL
−25% to 125%
77.9
RW
ALL
> = 0%, < =100%
77.10
RW
ALL
−25% to 125%
77.11
RW
ALL
> = 0%, < = 100%
77.12
RW
ALL
−25% to 125%
77.13
RW
ALL
> = 0%, < = 100%
77.14
RW
ALL
−25% to 125%
77.15
RW
ALL
> = 0%, < = 100%
77.16
RW
ALL
−25% to 125%
77.17
RW
ALL
> = 0%, < = 100%
77.18
RW
ALL
−25% to 125%
77.19
RW
ALL
> = 0%, < = 100%
−Continued−
Protect
Initial Value
Category
Data Type: Float
5%
SETUP
Alerts when difference between sp
and pv is too large for too long.
10 sec
SETUP
Data Type: Float
2%
SETUP
Data Type: Float
Data Type: Uint32
Alerts when accumulated travel is
1,000,000
SETUP
too much
Data Type: Float
1%
SETUP
Deadband
Alerts when number of cycles is too
1,000,000
SETUP
large.
Data Type: Float
1%
SETUP
Deadband
Data Type: Float
Alert when valve is open. Control
99.5%
SETUP
DI channel 24 regardless of alert
enable state.
Data Type: Float
5%
SETUP
Deadband
Data Type: Float
Alerts when valve closed. Controls
0.5%
SETUP
DI channel 25 regardless of alert
enable state.
Data Type: Float
5%
SETUP
Deadband
Data Type: Float
Alert when valve position is less
than alert point. Controls DI
−25%
SETUP
channels 26 & 30 regardless of
alert enable state.
Data Type: Float
5%
SETUP
Deadband
Data Type: Float
Alert when valve position is less
−25%
SETUP
than alert point. Controls DI
channels 27 & 31 regardless of
alert enable state.
Data Type: Float
5%
SETUP
Deadband
Data Type: Float
Alert when valve position is less
125%
SETUP
than alert point. Controls DI
channels 28 & 32 regardless of
alert enable state.
Data Type: Float
5%
SETUP
Deadband
Data Type: Float
Alert when valve position is less
125%
SETUP
than alert point. Controls DI
channels 29 & 33 regardless of
alert enable state.
Data Type: Float
5%
SETUP
Deadband