Table 9-3. Set Up For Digital Operator Control - YASKAWA GPD 515/G5 Modbus RTU Technical Manual

Hide thumbs Also See for GPD 515/G5 Modbus RTU:
Table of Contents

Advertisement

Table 9-3: Set up for Digital Operator Control
This table indicates the functions or commands that can be accessed via serial communication,
external terminals, or the digital operator when the driveís parameter b1-02 is set up for digital
operator control (b1-02 = 0). The ìOî indicates that the function is Operable from that source,
and ìn/aî indicates that the function is not available from that source.
From
Regis
ter
001h
SERIAL
COMM.
007h
008h
009h
Forward Run (2 wire); Run Command (3 wire)
Reverse Run (2 wire); Stop Command (3 wire)
multi-function input terminal 3
EXTERNAL
multi-function input terminal 4
TERMINALS
multi-function input terminal 5
multi-function input terminal 6
multi-function input terminal 7
multi-function input terminal 8
Run Command
Stop Command
Reverse Run Command
DIGITAL
Local / Remote
OPERATOR
Jog Command
Fault Reset
Notes:
1. Fault Reset (Multi-function Input terminal 4 default setting) is only effective only when in stopped
condition.
2. The availability of the multi-function input terminals vary depending upon the settings of H1-01,
H1-02, H1-03, H1-04, H1-05, H1-06 (the multi-function input settings), and A1-02 (Control
Method). See technical manual TM4515.
3. The jog command is only effective when in the stop condition.
Bit
Data Description
No.
0
Run Forward
1
Run Reverse
2
Multi-function Input (terminal 3)
3
Multi-function Input (terminal 4)
4
Multi-function Input (terminal 5)
5
Multi-function Input (terminal 6)
6
Multi-function Input (terminal 7)
7
Multi-function Input (terminal 8)
8-15
unused
0-15
Analog Output 1 Setting
0-15
Analog Output 2 Setting
0
Multi-function Output 1
1
Multi-function Output 2
2
Multi-function Output 3
3-5
unused
6
Fault Contact (terminals 18 & 20)
7
Fault Contact Closed (effective when bit 6=1)
Function
Availability
n/a
n/a
O
O (1)
O
O
O
O
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
(2)
(2)
(2)
(2)
(2)
(2)
O
O
O
n/a
O (3)
O (1)
Command Priority
9-5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents