Drive Parameter Registers (Read/Write) (continued)
REGISTER PARAMETER
(in hex)
415h
H4-01
416h
H4-02
417h
H4-03
418h
H4-04
419h
H4-05
41Ah
H4-06
41Bh
H4-07
41Ch
H5-01
41Dh
H5-02
41Eh
H5-03
41Fh
H5-04
420h
H5-05
7-22
PARAMETER
FUNCTION
Multi-function Analog Monitor 1
Selection (terminal 21)
Multi-function Analog Monitor 1 Gain
Multi-function Analog Monitor 1 Bias
Multi-function Analog Monitor 2
Selection (terminal 23)
Multi-function Analog Monitor 2 Gain
Multi-function Analog Monitor 2 Bias
Multi-function Analog Monitor Signal
Level Selection (terminal 21 & 23)
Serial Communication Address
Serial Communication Baud Rate
Serial Communication
Parity Selection
Stopping Method after Serial
Communication Error
Communication Error (CE) Detection
Selection
PARAMETER
LIMITS / DESCRIPTION
SETTING
1 to 31h
0.00 to 2.50
-10.0 to +10.0%
1 to 31h
0.00 to 2.50
-10.0 to +10.0%
0
1
-10 to +10 V DC
0 to 1Fh
0
1
2
3
0
1
2
0
1
2
3
0
1
Registers
0 to 10 V DC
1200 bps
2400 bps
4800 bps
9600 bps
No Parity
Even Parity
Odd Parity
Ramp to Stop
Coast to Stop
Fast-Stop
Alarm Only
Disabled
Enabled
INITIAL
VALUE
2
1.00
0.0
3
0.50
0.0
0
1Fh
3
0
3
1