YASKAWA GPD 515/G5 Modbus RTU Technical Manual page 56

Hide thumbs Also See for GPD 515/G5 Modbus RTU:
Table of Contents

Advertisement

Drive Parameter Registers (Read/Write) (continued)
REGISTER PARAMETER
(in hex)
38Dh
F2-01
38Eh
F3-01
38Fh
F4-01
390h
F4-02
391h
F4-03
392h
F4-04
393h
F5-01
394h
F5-02
395h
F6-01
396h
F7-01
Notes:
1. Range shown is for flash software version '1030' and CPU version '30'. Range differs for previous versions.
7-20
PARAMETER
FUNCTION
AI-14 Bi-polar or Uni-polar Input
Selection
DI-16 Digital Input Option
AO-08/AO-12 Channel 1 Monitor Select.
AO-08/AO-12 Channel 1 Gain
AO-08/AO-12 Channel 2 Monitor Select.
AO-08/AO-12 Channel 2 Gain
DO-02 Channel 1 Output Selection
DO-02 Channel 2 Output Selection
DO-08 Output Mode Selection
PO-36F Frequency Multiple
Selection
PARAMETER
LIMITS / DESCRIPTION
SETTING
0
3-channel Individual
1
3-channel Addition
0
1
2
3
4
5
BCD 0.01 Hz
6
BCD (5DG) 0.01 Hz
7
1 to 33h (1)
0.00 to 2.50
1 to 33h (1)
0.00 to 2.50
0 to Fh
0 to Fh
0
8-channel Individual
1
Binary Output
0
1 x Output Frequency
1
6 x Output Frequency
2
10 x Output Frequency
3
12 x Output Frequency
4
36 x Output Frequency
Registers
INITIAL
VALUE
BCD 1%
BCD 0.1%
BCD 0.01%
BCD 1 Hz
BCD 0.1 Hz
Binary
0
0
2
1.00
3
0.50
0
1
0
1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents