Drive Parameter Registers (Read/Write) (continued)
REGISTER PARAMETER
(in hex)
180h
b1-01
181h
b1-02
182h
b1-03
183h
b1-04
184h
b1-05
185h
b1-06
186h
b1-07
187h
b2-01
188h
b2-02
189h
b2-03
18Ah
b2-04
18Bh-18Dh
7-12
PARAMETER
FUNCTION
Reference Selection
Operation Method Selection
Stopping Method Selection
Reverse Operation Prohibit
Zero Speed Operation
(level determined by E1-09)
Logic Input Scan Rate
Local / Remote RUN Selection
DC Injection Braking Start
Frequency
DC Injection Braking Current
DC Injection Braking Time at Start
DC Injection Braking Time at Stop
Reserved
PARAMETER
LIMITS / DESCRIPTION
SETTING
0
Digital Operator
1
2
Serial Communication
3
Option PCB
0
Digital Operator
1
2
Serial Communication
3
Option PCB
0
Ramp to Stop
1
Coast to Stop
2
DC Injection to Stop
3
Coast with Timer
0
Enable Reverse Operation
1
Disable Reverse Operation
0
Run at Frequency Reference
1
2
Run at Min. Frequency (E1-09)
3
Run at Zero Speed
0
2ms - 2 scans
1
5ms - 2 scans
0
Cycle External Run
1
Accept External Run
0.0 to 10.0 Hz
0 - 100%
0.00 - 10.00 seconds
0.00 - 10.00 seconds
Registers
INITIAL
VALUE
Terminal
Terminal
Stop
0.00
0.00
1
1
0
0
0
1
0
0.5
50