Drive Parameter Registers (Read/Write) (continued)
REGISTER PARAMETER
(in hex)
400h
H1-01
401h
H1-02
402h
H1-03
403h
H1-04
404h
H1-05
405h
H1-06
406h
H2-01
407h
H2-02
408h
H2-03
409h
H3-01
40Ah
H3-02
40Bh
H3-03
40Ch
H3-04
40Dh
H3-05
40Eh
H3-06
40Fh
H3-07
410h
H3-08
411h
H3-09
412h
H3-10
413h
H3-11
414h
H3-12
Notes:
1. Initial value in the parentheses are values obtained at a 3-wire initialization.
7-21
PARAMETER
FUNCTION
Multi-function Input (terminal 3)
Multi-function Input (terminal 4)
Multi-function Input (terminal 5)
Multi-function Input (terminal 6)
Multi-function Input (terminal 7)
Multi-function Input (terminal 8)
Multi-function Output (term. 9 & 10)
Multi-function Output (term. 25-27)
Multi-function Output (term. 26-27)
Auto Speed Reference Signal
Level Selection (term. 13)
Auto Speed Reference Signal Gain
Auto Speed Reference Signal Bias
Multi-function Analog Input 1 Signal
Level Selection (term. 16)
Multi-function Analog Input 1 Select.
Multi-function Analog Input 1 Gain
Multi-function Analog Input 1 Bias
Multi-function Analog Input 2 Signal
Level Selection (term. 14)
Multi-function Analog Input 2 Select.
Multi-function Analog Input 2 Gain
Multi-function Analog Input 2 Bias
Analog Input Filter Time Constant
PARAMETER
LIMITS / DESCRIPTION
SETTING
0 to 77h
0 to 77h
0 to 77h
0 to 77h
0 to 77h
0 to 77h
0 to 37h
0 to 37h
0 to 37h
0
0 to 10 V DC
1
-10 to +10 V DC
0.0 to 1000.0%
-100.0 to +100.0%
0
0 to 10 V DC
1
-10 to +10 V DC
0 to 1Fh
0.0 to 1000.0%
-100.0 to +100.0%
0
0 to 10 V DC
1
-10 to +10 V DC
2
0 to 1Fh
0.0 to 1000.0%
-100.0 to +100.0%
0.00 to 2.00 seconds
Registers
INITIAL
VALUE
3 (or 0) (1)
4 (or 3) (1)
6 (or 4) (1)
8 (or 6) (1)
4 to 20 mA
24h
14h
0
1
2
0
100.0
0.0
0
0
100.0
0.0
2
1Fh
100.0
0.0
0.00

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents