Simultaneous Broadcast Registers (Write only)
REGISTER
FUNCTION
(in hex)
001*
Operational Signals
002*
Frequency Reference
Notes:
1. Scaling depends on the setting of o1-03.
* Set parameter o2-09 to '1' so that the Modbus Register Address of the Operation Signals register is 01h and the Frequency Reference register is 02h. The
Modbus Register Address for Operation Signals register is 00h and the Frequency Reference is 01h for flash software versions previous to '1024'
and CPU version '20'.
7-2
BIT
DATA
NO.
SET
0
0
1
1
0
1
2
3
4
1
5
1
6
7
Registers
DESCRIPTION
Stop
Run
Forward Run
Reverse Run
not used
not used
External Fault
Fault Reset
not used
not used
Frequency Reference (6000 = 100%) (1)