Drive Parameter Registers (Read/Write) (continued)
REGISTER PARAMETER
(in hex)
200h
C1-01
201h
C1-02
202h
C1-03
203h
C1-04
204h
C1-05
205h
C1-06
206h
C1-07
207h
C1-08
208h
C1-09
209h
C1-10
20Ah
C1-11
20Bh
C2-01
20Ch
C2-02
20Dh
C2-03
20Eh
C2-04
20Fh
C3-01
210h
C3-02
211h
C3-03
212h
C3-04
Notes (for this page only):
1. Values are dependent upon C1-10 setting.
2. Initial setting differs depending on the Control Method (A1-02).
7-14
PARAMETER
FUNCTION
Acceleration Time 1
Deceleration Time 1
Acceleration Time 2
Deceleration Time 2
Acceleration Time 3
Deceleration Time 3
Acceleration Time 4
Deceleration Time 4
Fast Stop Deceleration Time
Accel / Decel Time Setting Unit
Accel / Decel Time Switching Freq.
S-curve Characteristic at Accel Start
S-curve Characteristic at Accel End
S-curve Characteristic at Decel Start
S-curve Characteristic at Decel End
Slip Compensation Gain
Slip Compensation Primary Delay
Time
Slip Compensation Limit
Slip Compensation Selection
during Regeneration
PARAMETER
LIMITS / DESCRIPTION
SETTING
0.00 to 600.00 or 0.0 to 6000.0 seconds (1)
0.00 to 600.00 or 0.0 to 6000.0 seconds (1)
0.00 to 600.00 or 0.0 to 6000.0 seconds (1)
0.00 to 600.00 or 0.0 to 6000.0 seconds (1)
0.00 to 600.00 or 0.0 to 6000.0 seconds (1)
0.00 to 600.00 or 0.0 to 6000.0 seconds (1)
0.00 to 600.00 or 0.0 to 6000.0 seconds (1)
0.00 to 600.00 or 0.0 to 6000.0 seconds (1)
0.00 to 600.00 or 0.0 to 6000.0 seconds (1)
0
0.01 seconds
1
0.0 to 400.0 Hz
0.0 to 2.50 seconds
0.0 to 2.50 seconds
0.0 to 2.50 seconds
0.0 to 2.50 seconds
0.0 to 2.5
0 to 10000 msec.
0 to 250%
0
1
Registers
INITIAL
VALUE
10.0 (1)
10.0 (1)
10.0 (1)
10.0 (1)
10.0 (1)
10.0 (1)
10.0 (1)
10.0 (1)
10.0 (1)
0.1 seconds
Disabled
Enabled
1
0.00
0.20
0.20
0.20
0.20
(2)
(2)
200
0