Drive Parameter Registers (Read/Write) (continued)
REGISTER PARAMETER
(in hex)
48Dh
L3-06
48E-48Fh
490h
L4-01
491h
L4-02
492h
L4-03
493h
L4-04
494h
L4-05
495h
L5-01
496h
L5-02
497h
L5-03
498h
L6-01
499h
L6-02
49Ah
L6-03
49Bh
L6-04
7-24
PARAMETER
FUNCTION
Stall Prevention Level during Running
Reserved
Speed Coincidence Frequency
Speed Coincidence Width
Speed Coincidence Frequency (+/-)
Speed Coincidence Width (+/-)
Frequency Reference Loss
Detection
Number of Auto Restart Attempts
Auto Restart Operation Selection
Fault Restart Time
Torque Detection Selection 1
Torque Detection Level 1
Torque Detection Time 1
Torque Detection Selection 2
PARAMETER
LIMITS / DESCRIPTION
SETTING
30 to 200%
0.0 to 400.0 Hz
0.0 to 20.0 Hz
-400.0 to +400.0 Hz
0.0 to 20.0 Hz
0
1
Run at 80% of Frequency Reference
0 to 10
0
No Fault Relay
1
Fault Relay Active
0.5 to 180.0 seconds
0
1
Detected during Speed Agree
(operation continues)
2
Detected during Running (operation
3
Detected during Speed Agree (drive
4
Detected during Running (drive faults)
0 to 300%
0.0 to 10.0 seconds
0
1
Detected during Speed Agree
(operation continues)
2
Detected during Running (operation
3
Detected during Speed Agree (drive
4
Detected during Running (drive faults)
Registers
INITIAL
VALUE
Stop
Disabled
continues)
faults)
Disabled
continues)
faults)
160
0.0
2.0
0.0
2.0
0
0
0
10.0
0
150
0.1
0