Basic functions

3
Basic functions
3.1

General parameters

3.1.1

Analog input settings, phase currents

Table 6: Analog input settings, phase currents
Parameter
Values (Range)
Primary current
1.0...6000.0
1
Secondary current
2=1A
3=5A
Amplitude Corr A
0.9000...1.1000
Amplitude Corr B
0.9000...1.1000
Amplitude Corr C
0.9000...1.1000
2
Nominal current
39...4000
Rated secondary
1.000...150.000
Val
Reverse polarity
0=False
1=True
Angle Corr A
-8.000 ... 8.000
Angle Corr B
-8.000 ... 8.000
Angle Corr C
-8.000 ... 8.000
1
For CT
2
For sensor
50
Unit
Step
A
0.1
0.0001
0.0001
0.0001
A
1
mV/Hz
0.001
deg
0.0001
deg
0.0001
deg
0.0001
1MRS757644 H
Default
Description
100.0
Rated primary cur-
rent
2=1A
Rated secondary
current
1.0000
Phase A amplitude
correction factor
1.0000
Phase B amplitude
correction factor
1.0000
Phase C amplitude
correction factor
1300
Network Nominal
Current (In)
3.000
Rated Secondary
Value (RSV) ratio
0=False
Reverse the polari-
ty of the phase CTs
0.0000
Phase A angle cor-
rection factor
0.0000
Phase B angle cor-
rection factor
0.0000
Phase C angle cor-
rection factor
Technical Manual