2. How to Programme
[60]
[61]
[63]
2
[64]
5-16 Terminal X30/3 Digital Input
Option:
[0]
5-17 Terminal X30/4 Digital Input
Option:
[0]
5-18 Terminal X30/4 Digital Input
Option:
[0]
5-19 Terminal 37 Safe Stop
Option:
[1]
[3]
[4]
[5]
[6]
[7]
100
Counter A (up)
Counter A (down)
Counter B (up)
Counter B (down)
*
No operation
*
No operation
*
No operation
*
Safe Stop Alarm
Safe Stop Auto Reset Coasts frequency converter when safe stop is activated (term
PTC 1 Alarm
PTC 1 Warning
PTC 1 & Relay A
PTC 1 & Relay W
MG.33.M2.02 - VLT
Function:
This parameter is active when option module MCB 101 is instal-
led in the frequency converter.
Follow the function stated in 5-1*
Function:
This parameter is active when option module MCB 101 is instal-
led in the frequency converter.
Follow the function stated in 5-1*
Function:
This parameter is active when option module MCB 101 is instal-
led in the frequency converter.
Follow the function stated in 5-1*
Function:
Coasts frequency converter when safe stop is activated. Manual
reset from LCP, digital input or fieldbus.
37 off). When safe stop circuit is reestablished, the drive will
continue without manual reset.
Coasts frequency converter when safe stop is activated. Manual
reset from LCP, digital input or fieldbus. Choice 4 is only avail-
able when the MCB 112 PTC Thermistor Card is connected.
Coasts frequency converter when safe stop is activated (term
37 off). When safe stop circuit is reestablished, the drive will
continue without manual reset, unless a Digital Input set to PTC
Card 1 [80] is still enabled. Choice 5 is only available when the
MCB 112 PTC Thermistor Card is connected.
This choice is used when the PTC option is gated together with
a Stop button through a Safety relay to T-37. Coasts frequency
converter when safe stop is activated. Manual reset from LCP,
digital input or fieldbus. Choice 6 is only available when the MCB
112 PTC Thermistor Card is connected.
This choice is used when the PTC option is gated together with
a Stop button through a Safety relay to T-37. Coasts frequency
converter when safe stop is activated (term 37 off). When safe
stop circuit is reestablished, the drive will continue without man-
®
is a registered Danfoss trademark