2. How to Programme
13-03 Reset SLC
Option:
[0]
2
[1]
2.14.3. 13-1* Comparators
Comparators are used for comparing continuous variables (i.e. output frequency, output current,
analog input etc.) to fixed preset values. In addition, there are digital values that will be compared
to fixed time values. See explanation in par. 13-10. Comparators are evaluated once in each scan
interval. Use the result (TRUE or FALSE) directly. All parameters in this parameter group are array
parameters with index 0 to 5. Select index 0 to programme Comparator 0, select index 1 to pro-
gramme Comparator 1, and so on.
13-10 Comparator Operand
Array [6]
Choice [1] to [31] are variables which will be compared based on their values. Choice [50] to [186]
are digital values (TRUE/FALSE) where the comparison is based on the amount of time during
which they are set to TRUE or FALSE, respectively. See par. 13-11.
Select the variable to be monitored by the comparator.
[0]
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
[9]
[10]
[11]
[12]
[13]
[14]
[15]
[17]
158
*
Do not reset SLC
Reset SLC
*
DISABLED
Reference
Feedback
Motor speed
Motor current
Motor torque
Motor power
Motor voltage
DC-link voltage
Motor thermal
VLT thermal
Heat sink temp.
Analog input AI53
Analog input AI54
Analog input AIFB10
Analog input AIS24V
Analog input AICCT
MG.33.M2.02 - VLT
Function:
Retains programmed settings in all group 13 parameters (13-*).
Resets all group 13 parameters (13-*) to default settings.
DISABLED
[0] The comparator is disabled.
Reference
[1] The resulting remote reference (not local) as a
percentage.
Feedback
[2] In the unit [RPM] or [Hz]
Motor speed
[3] [RPM] or [Hz]
Motor current
[4] [A]
Motor torque
[5] [Nm]
Motor power
[6] [kW] or [hp]
Motor voltage
[7] [V]
DC-link voltage
[8] [V]
Motor thermal
[9] Expressed as a percentage.
VLT thermal
[10] Expressed as a percentage.
Heat sink temp
[11] Expressed as a percentage.
Analog input AI53
[12] Expressed as a percentage.
Analog input AI54
[13] Expressed as a percentage.
Analog input AIFB10
[14] [V]
Analog input AIS24V
[15] [V] Analog input AICCT [17] [°].
®
is a registered Danfoss trademark
FC 300 Programming Guide