Danfoss FC 300 Programming Manual page 80

Hide thumbs Also See for FC 300:
Table of Contents

Advertisement

2. How to Programme
3-55 Ramp 2 S-ramp Ratio at Accel. Start
Range:
50%
2
3-56 Ramp 2 S-ramp Ratio at Accel. End
Range:
50%
3-57 Ramp 2 S-ramp Ratio at Decel. Start
Range:
50%
3-58 Ramp 2 S-ramp Ratio at Decel. End
Range:
50%
2.6.6. 3-6* Ramp 3
Configure ramp parameters, see 3-4*.
3-60 Ramp 3 Type
Option:
[0]
[1]
[2]
80
*
[1 - 99%]
*
[1 - 99%]
*
[1 - 99%]
*
[1 - 99%]
*
Linear
S-ramp Const Jerk
S-ramp Const Time
NB!
If S-ramp [1] is selected and the reference during ramping is changed the ramp time
may be prolonged in order to realize a jerk free movement which may result in a
longer start or stop time.
Additional adjustment of the S-ramp ratios or switching initiators may be necessary.
MG.33.M2.02 - VLT
Function:
Enter the proportion of the total ramp-up time (par. 3-51) in
which the acceleration torque increases. The larger the per-
centage value, the greater the jerk compensation achieved, and
thus the lower the torque jerks in the application.
Function:
Enter the proportion of the total ramp-up time (par. 3-51) in
which the acceleration torque decreases. The larger the per-
centage value, the greater the jerk compensation achieved, and
thus the lower the torque jerks in the application.
Function:
Enter the proportion of the total ramp-down time (par. 3-52)
where the deceleration torque increases The larger the per-
centage value, the greater the jerk compensation achieved, and
thus the lower the torque jerks in the application.
Function:
Enter the proportion of the total ramp-down time (par. 3-52)
where the deceleration torque decreases. The larger the per-
centage value, the greater the jerk compensation achieved, and
thus the lower the torque jerks in the application.
Function:
Select the ramp type, depending on requirements for accelera-
tion and deceleration. A linear ramp will give constant acceler-
ation during ramping. An S-ramp will give non-linear accelera-
tion, compensating for jerk in the application.
Accelerates with lowest possible jerk.
S-ramp based on the values set in par. 3-61 and 3-62
®
is a registered Danfoss trademark
FC 300 Programming Guide

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents