FC 300 Programming Guide
1-91 Motor External Fan
Option:
*
[0]
[1]
1-93 Thermistor Source
Option:
*
[0]
[1]
[2]
[3]
[4]
[5]
[6]
Function:
No
No external fan is required, i.e. the motor is derated at low
speed.
Yes
Applies an external motor fan (external ventilation), so no de-
rating of the motor is required at low speed. The graph below
is followed if the motor current is lower than nominal motor
current (see par. 1-24). If the motor current exceeds nominal
current, the operation time still decreases as if no fan were in-
stalled.
Function:
Select the input to which the thermistor (PTC sensor) should be
connected. An analog input option [1] or [2] cannot be selected
if the analog input is already in use as a reference source (se-
lected in par. 3-15
2 or 3-17 Reference Source 3).
This parameter cannot be adjusted while the motor is running.
None
Analog input 53
Analog input 54
Digital input 18
Digital input 19
Digital input 32
Digital input 33
®
MG.33.M2.02 - VLT
is a registered Danfoss trademark
2. How to Programme
Reference Source
Reference Source
1, 3-16
2
61