2. How to Programme
0-11 Edit Set-up
Option:
2
[0]
[1]
[2]
[3]
[4]
[9]
0-12 This Set-up Linked to
Option:
30
Factory setup
*
Set-up 1
Set-up 2
Set-up 3
Set-up 4
Active Set-up
MG.33.M2.02 - VLT
Function:
Select the set-up to be edited (i.e. programmed) during opera-
tion; either the active set-up or one of the inactive set-ups.
Cannot be edited but it is useful as a data source to return the
other set-ups to a known state.
Set-up 1
Set-up 4
[1] to
[4] can be edited freely during opera-
tion, independently of the active set-up.
Can also be edited during operation. Edit the chosen set-up from
a range of sources: LCP, FC RS485, FC USB or up to five fieldbus
sites.
Function:
To enable conflict-free changes from one set-up to another dur-
ing operation, link set-ups containing parameters which are not
changeable during operation. The link will ensure synchronising
of the 'not changeable during operation' parameter values when
moving from one set-up to another during operation. 'Not
changeable during operation' parameters can be identified by
®
is a registered Danfoss trademark
FC 300 Programming Guide