2. How to Programme
This parameter cannot be adjusted while the motor is running.
1-03 Torque Characteristics
Option:
2
[0]
[1]
[2]
This parameter cannot be adjusted while the motor is running.
1-04 Overload Mode
Option:
[0]
[1]
This parameter cannot be adjusted while the motor is running.
1-05 Local Mode Configuration
Option:
[0]
[1]
[2]
2.4.2. 1-1* Motor selection
Parameter group for setting general motor data.
This parameter group cannot be adjusted while the motor is running.
1-10 Motor Construction
Option:
[0]
[1]
44
*
Constant torque
Variable torque
Auto energy optim.
*
High torque
Normal torque
Speed open loop
Speed closed loop
*
As mode par. 1-00
*
Asynchronous
PM, non salient SPM
(FC 302 only)
MG.33.M2.02 - VLT
Function:
Select the torque characteristic required.
VT and AEO are both energy saving operations.
Motor shaft output provides constant torque under variable
speed control.
Motor shaft output provides variable torque under variable
speed control. Set the variable torque level in par. 14-40
Level
.
Automatically optimises energy consumption by minimising
magnetisation and frequency via par. 14-41
netisation
and par. 14-42
Minimum AEO Frequency
Function:
Allows up to 160% over torque.
For oversized motor - allows up to 110% over torque.
Function:
Select which application configuration mode (par. 1-00), i.e. ap-
plication control principle, to use when a Local (LCP) Reference
is active. A Local Reference can be active only when par. 3-13
Reference Site
is set to [0] or [2]. By default the local reference
is active in Hand Mode only.
Function:
Select the motor construction type.
For asynchronous motors.
For permanent magnet (PM) motors.
®
is a registered Danfoss trademark
FC 300 Programming Guide