FC 300 Programming Guide
4-14 Motor Speed High Limit [Hz]
Range:
Size re-
lated
4-16 Torque Limit Motor Mode
Range:
160.0 %
*
NB!
Max. output frequency cannot exceed 10% of the inverter switching frequency (par.
14-01).
Function:
[0 - 1000 Hz]
Enter the maximum limit for motor speed. The Motor Speed
*
High Limit can be set to correspond to the manufacturer's rec-
ommended maximum frequency of the motor shaft. The Motor
Speed High Limit must exceed the setting in par. 4-12
Speed Low Limit [Hz]
depending on other parameters set in the Main Menu and de-
pending on default settings dependant on global geographical
location.
NB!
Max. output frequency cannot exceed 10% of the inverter switching frequency (par.
14-01).
Function:
[0.0 - Variable Limit
Sets the torque limit for motor operation. The torque limit is
%]
active in the speed range up to the rated motor speed (par.
1-25). To protect the motor from reaching the stalling torque,
the default setting is 1.6 x the rated motor torque (calculated
value). If a setting in par. 1-00 to par. 1-26 is changed, par.
4-16 to 4-18 are not automatically reset to the default settings.
Torque Limit Motor Mode
Changing par. 4-16
loop
Min Current at Low Speed
[0], par. 1-66
®
MG.33.M2.02 - VLT
is a registered Danfoss trademark
2. How to Programme
. Only par. 4-11 or 4-12 will be displayed
when par. 1-00 is set to
is automatically readjusted.
2
Motor
Speed open
87