Running / no warning Output speed is higher than the speed set in par. 1-81
for Function at Stop [RPM]
no warnings.
Run in range / no
Motor is running within the programmed current and speed
warning
ranges set in par. 4-50 to par. 4-53. There are no warnings.
Run on reference / no
Motor runs at reference speed.
warning
Alarm
An alarm activates the output. There are no warnings.
Alarm or warning
An alarm or a warning activates the output.
At torque limit
The torque limit set in par. 4-16 or par. 1-17 has been exceeded.
Out of current range
The motor current is outside the range set in par. 4-18.
Below current, low
Motor current is lower than set in par. 4-50.
Above current, high
Motor current is higher than set in par. 4-51.
Out of range
Output frequency is outside the frequency range set in any limit
parameter.
Below speed, low
Output speed is lower than the setting in par. 4-52.
Above speed, high
Output speed is higher than the setting in par. 4-53.
Out of feedback range Feedback is outside the range set in par. 4-56 and 4-57.
Below feedback low
Feedback is below the limit set in par. 4-56 Warning Feedback
Low.
Above feedback high Feedback is above the limit set in par. 4-57
High
.
Thermal warning
The thermal warning turns on when the temperature exceeds
the limit in the motor, the frequency converter, the brake resis-
tor, or the thermistor.
Ready,
no
thermal
Frequency converter is ready for operation and there is no over-
warning
temperature warning.
Remote, ready, no
Frequency converter is ready for operation and is in Auto On
thermal warning
mode. There is no over-temperature warning.
Ready, no over-/ un-
Frequency converter is ready for operation and the mains volt-
der voltage
age is within the specified voltage range (see
cations
Reversing. Logic '1'
Reverse
when CCW rotation of the motor. If the motor is not rotating the
output will follow the reference.
Bus OK
Active communication (no time-out) via the serial communica-
tion port.
Torque limit and stop Use in performing a coasting stop and in torque limit condition.
If the frequency converter has received a stop signal and is at
the torque limit, the signal is Logic '0'.
Brake, no brake warn-
Brake is active and there are no warnings.
ing
MG.33.M2.02 - VLT
. The motor is running and there are
section).
when CW rotation of the motor. Logic '0'
®
is a registered Danfoss trademark
FC 300 Programming Guide