FC 300 Programming Guide
Array [1000]
Read only
9-27 Parameter Edit
Option:
[0]
Disabled
*
Enabled
[1]
9-28 Process Control
Option:
[0]
Disable
*
Enable cyclic master
[1]
9-44 Fault Message Counter
Range:
*
0
[0-65535]
9-45 Fault Code
Range:
*
0
[0 - 0]
9-47 Fault Number
Range:
*
0
[0 - 0]
9-52 Fault Situation Counter
Range:
*
0
[0 - 1000]
9-53 Profibus Warning Word
This parameter displays Profibus communication warnings. Please refer to the
further information.
Read only
This parameter contains a list of signals available for selection in par. 9-15 and 9-16.
Function:
Parameters can be edited via Profibus, the standard RS485 interface, or the LCP.
Disables editing via Profibus.
Enables editing via Profibus.
Function:
Process control (setting of Control Word, speed reference, and process data) is possible via either Profibus or
standard fieldbus but not both simultaneously. Local control is always possible via the LCP. Control via process
control is possible via either terminals or fieldbus depending on the settings in par. 8-50 to 8-56.
Disables process control via Profibus, and enables process control via standard fieldbus or Profibus Master class
2.
Enables process control via Profibus Master Class 1, and disables process control via standard fieldbus or Profibus
Master class 2.
Function:
This parameter displays the number of error events stored in par. 9-45 and 9-47. The maximum buffer capacity
is eight error events. The buffer and counter are set to 0 upon reset or power-up.
Function:
This buffer contains the alarm word for all alarms and warnings that have occurred since last reset or power-up.
The maximum buffer capacity is eight error events.
Function:
This buffer contains the alarm number (e.g. 2 for live zero error, 4 for mains phase loss) for all alarms and
warnings that have occurred since last reset or power-up. The maximum buffer capacity is eight error events.
Function:
This parameter displays the number of error events which have occurred since last reset of power-up.
®
MG.33.M3.02 - VLT
is a registered Danfoss trademark
2. How to Programme
Profibus Operating Instructions
2
for
115