Danfoss FC 300 Programming Manual page 52

Hide thumbs Also See for FC 300:
Table of Contents

Advertisement

2. How to Programme
2
Using a digital input and 10 V as power supply:
Example: The frequency converter trips when the motor temperature is too high.
Parameter set-up:
Motor Thermal Protection
Set Par. 1-90
Thermistor Source
Set Par. 1-93
Using an analog input and 10 V as power supply:
Example: The frequency converter trips when the motor temperature is too high.
Parameter set-up:
Motor Thermal Protection
Set Par. 1-90
Thermistor Source
Set Par. 1-93
Input
Digital/analog
Digital
Digital
Analog
52
Thermistor Trip
to
[2]
Digital Input
to
[6]
Thermistor Trip
to
[2]
Analog Input 54
to
[2]
Supply Voltage
Volt
24 V
10 V
10 V
MG.33.M3.02 - VLT
Threshold
Cut-out Values
< 6.6 kΩ - > 10.8 kΩ
< 800Ω - > 2.7 kΩ
< 3.0 kΩ - > 3.0 kΩ
®
is a registered Danfoss trademark
FC 300 Programming Guide

Advertisement