2. How to Programme
17-59 Resolver Interface
Option:
*
Disabled
[0]
2
[1]
Enabled
2.18.5. 17-6* Monitoring and Application
This parameter group is for selecting additional functions when MCB 102 Encoder option or MCB 103 Resolver option is fitted into option slot B as speed
feedback.
Monitoring and Application parameters cannot be adjusted while the motor is running.
17-60 Encoder Positive Direction
Option:
*
Clockwise
[0]
[1]
Counter clockwise
17-61 Encoder Signal Monitoring
Option:
[0]
Disabled
*
Warning
[1]
[2]
Trip
166
The value is stated in the data sheet for resolvers.
Function:
Activate the MCB 103 resolver option when the resolver parameters are selected.
To avoid damage to resolvers par. 17-50 – par. 17-53 must be adjusted before activating this parameter.
Function:
Change the detected encoder rotation direction without changing the wiring to the encoder.
This parameter cannot be adjusted while the motor is running.
Function:
Select which reaction the frequency converter should take in case a faulty encoder signal is detected.
The encoder function in par. 17-61 is an electrical check of the hardware circuit in the encoder system.
®
MG.33.M3.02 - VLT
is a registered Danfoss trademark
FC 300 Programming Guide