FC 300 Programming Guide
6-53 Terminal 42 Output Bus Control
Range:
*
0.00%
[0.00 – 100.00 %]
6-54 Terminal 42 Output Timeout Preset
Range:
*
0.00%
[0.00 – 100.00 %]
2.9.8. 6-6* Analog Output 2 (MCB 101)
Analog outputs are current outputs: 0/4 - 20 mA. Common terminal (terminal X30/8) is the same terminal and electrical potential for analog common
connection. Resolution on analog output is 12 bit.
6-60 Terminal X30/8 Output
Option:
[0]
No operation
[100]
Output frequency (0 .
1000 Hz), 0.20 mA
[101]
Output frequency (0 .
1000 Hz), 4.20 mA
Reference
(Refmin-
max),0.20 mA
[102]
Reference (Ref min-
max), 4.20 mA
Feedback
(FB
max)0.20 mA
[103]
Feedback
(FB
max) 4.20 mA
Motor current (0-Imax)
0.20 mA
[104]
Motor current (0-Imax)
4.20 mA
Torque relative to lim-
it0-Tlim,0.20 mA
[105]
Torque relative to limit
0-Tlim, 4.20 mA
Torque
relativetora-
ted0-Tnom,0.20 mA
[106]
Torque relative to rated
0-Tnom, 4.20 mA
Power
(0-Pnom),0.20
mA
Function:
Holds the level of Output 42 if controlled by bus.
Function:
Holds the preset level of Output 42.
In case of a bus timeout and a timeout function is selected in par. 6-50 the output will preset to this level.
Function:
min-
min-
®
MG.33.M3.02 - VLT