Danfoss FC 300 Programming Manual page 86

Hide thumbs Also See for FC 300:
Table of Contents

Advertisement

2. How to Programme
[3]
Drive ready / remote
control
[4]
Enable / no warning
[5]
VLT running
2
[6]
Running / no warning
[7]
Run in range / no warn-
ing
[8]
Run on reference / no
warning
[9]
Alarm
[10]
Alarm or warning
[11]
At torque limit
[12]
Out of current range
[13]
Below current, low
[14]
Above current, high
[15]
Out of range
[16]
Below speed, low
[17]
Above speed, high
[18]
Out of feedback range
[19]
Below feedback low
[20]
Above feedback high
[21]
Thermal warning
[22]
Ready,
warning
[23]
Remote,
thermal warning
[24]
Ready, no over-/ under
voltage
[25]
Reverse
[26]
Bus OK
[27]
Torque limit and stop
[28]
Brake, no brake warn-
ing
[29]
Brake ready, no fault
[30]
Brake fault (IGBT)
[31]
Relay 123
[32]
Mechanical brake con-
trol
[33]
Safe stop activated (FC
302 only)
[40]
Out of ref range
[41]
Below reference low
[42]
Above reference high
[45]
Bus Ctrl
86
The frequency converter is ready for operation and is in Auto On mode.
Ready for operation. No start or stop command is been given (start/disable). There are no warnings.
Motor is running.
Output speed is higher than the speed set in par. 1-81
running and there are no warnings.
Motor is running within the programmed current and speed ranges set in par. 4-50 to par. 4-53. There are no
warnings.
Motor runs at reference speed.
An alarm activates the output. There are no warnings.
An alarm or a warning activates the output.
The torque limit set in par. 4-16 or par. 1-17 has been exceeded.
The motor current is outside the range set in par. 4-18.
Motor current is lower than set in par. 4-50.
Motor current is higher than set in par. 4-51.
Output frequency is outside the frequency range set in any limit parameter.
Output speed is lower than the setting in par. 4-52.
Output speed is higher than the setting in par. 4-53.
Feedback is outside the range set in par. 4-56 and 4-57.
Feedback is below the limit set in par. 4-56 Warning Feedback Low.
Feedback is above the limit set in par. 4-57
The thermal warning turns on when the temperature exceeds the limit in the motor, the frequency converter,
the brake resistor, or the thermistor.
no
thermal
Frequency converter is ready for operation and there is no over-temperature warning.
ready,
no
Frequency converter is ready for operation and is in Auto On mode. There is no over-temperature warning.
Frequency converter is ready for operation and the mains voltage is within the specified voltage range (see
General Specifications
Reversing. Logic '1'
when CW rotation of the motor. Logic '0' when CCW rotation of the motor. If the motor is
not rotating the output will follow the reference.
Active communication (no time-out) via the serial communication port.
Use in performing a coasting stop and in torque limit condition. If the frequency converter has received a stop
signal and is at the torque limit, the signal is Logic '0'.
Brake is active and there are no warnings.
Brake is ready for operation and there are no faults.
Output is Logic '1' when the brake IGBT is short-circuited. Use this function to protect the frequency converter
if there is a fault on the brake modules. Use the output/relay to cut out the main voltage from the frequency
converter.
Relay is activated when Control Word [0] is selected in parameter group 8-**.
Enables control of an external mechanical brake, see description in the section
par. group 2-2*
Indicates that the safe stop on terminal 37 has been activated.
MG.33.M3.02 - VLT
Min Speed for Function at Stop [RPM]
Warning Feedback High
section).
®
is a registered Danfoss trademark
FC 300 Programming Guide
. The motor is
.
Control of Mechanical Brake
, and