FC 300 Programming Guide
5-19 Terminal 37 Safe Stop
Option:
*
Safe Stop Alarm
[1]
[3]
Safe Stop Auto Reset
[4]
PTC 1 Alarm
[5]
PTC 1 Warning
[6]
PTC 1 & Relay A
[7]
PTC 1 & Relay W
[8]
PTC 1 & Relay A/W
[9]
PTC 1 & Relay W/A
NB!
When Auto Reset/ Warning is selected the frequency converter opens up for automatic restart.
Overview of functions, alarms and warnings
Function
No Function
Safe Stop Alarm
Safe Stop Warning
PTC 1 Alarm
PTC 1 Warning
PTC 1 & Relay A
PTC 1 & Relay W
PTC 1 & Relay A/W
PTC 1 & Relay W/A
W means warning and A means alarm. For further information, see Alarms and Warnings in section
Instructions
A dangerous failure related to Safe Stop will give Alarm: Dangerous Fail-
ure [A72].
2.8.4. 5-3* Digital Outputs
Parameters for configuring the output functions for the output terminals. The 2 solid-state digital outputs are common for terminals 27 and 29. Set the
I/O function for terminal 27 in par. 5-01
cannot be adjusted while the motor is running.
[0]
No operation
[1]
Control ready
[2]
Drive ready
Function:
Coasts frequency converter when safe stop is activated. Manual reset from LCP, digital input or fieldbus.
Coasts frequency converter when safe stop is activated (term 37 off). When safe stop circuit is reestablished,
the frequency converter will continue without manual reset.
Coasts frequency converter when safe stop is activated. Manual reset from LCP, digital input or fieldbus. Choice
4 is only available when the MCB 112 PTC Thermistor Card is connected.
Coasts frequency converter when safe stop is activated (term 37 off). When safe stop circuit is reestablished,
the frequency converter will continue without manual reset, unless a Digital Input set to PTC Card 1 [80] is still
enabled. Choice 5 is only available when the MCB 112 PTC Thermistor Card is connected.
This choice is used when the PTC option is gated together with a Stop button through a Safety relay to T-37.
Coasts frequency converter when safe stop is activated. Manual reset from LCP, digital input or fieldbus. Choice
6 is only available when the MCB 112 PTC Thermistor Card is connected.
This choice is used when the PTC option is gated together with a Stop button through a Safety relay to T-37.
Coasts frequency converter when safe stop is activated (term 37 off). When safe stop circuit is reestablished,
the frequency converter will continue without manual reset, unless a Digital Input set to PTC Card 1 [80] is (still)
enabled. Choice 7 is only available when the MCB 112 PTC Thermistor Card is connected.
This choice makes it possible to use a combination of Alarm and Warning. Choice 8 is only available when the
MCB 112 PTC Thermistor Card is connected.
This choice makes it possible to use a combination of Alarm and Warning. Choice 9 is only available when the
MCB 112 PTC Thermistor Card is connected.
No.
PTC
[0]
-
[1]*
-
[3]
-
[4]
PTC 1 Safe Stop [A71]
[5]
PTC 1 Safe Stop [W71]
[6]
PTC 1 Safe Stop [A71]
[7]
PTC 1 Safe Stop [W71]
[8]
PTC 1 Safe Stop [A71]
[9]
PTC 1 Safe Stop [W71]
Terminal 27 Mode
, and set the I/O function for terminal 29 in par. 5-02
Default for all digital outputs and relay outputs
The control board receives supply voltage.
The frequency converter is ready for operation and applies a supply signal on the control board.
®
MG.33.M3.02 - VLT
is a registered Danfoss trademark
2. How to Programme
Relay
-
Safe Stop [A68]
Safe Stop [W68]
-
-
Safe Stop [A68]
Safe Stop [W68]
Safe Stop [W68]
Safe Stop [A68]
Troubleshooting
in the Design Guide or the Operating
Terminal 29 Mode
. These parameters
2
85