1.1. Basic maintenance operations:

NEW ENGINE OR MAJOR SERVICE WORK START-UP MAINTENANCE
Jobs to be done during the initial start-up of a new engine or during the break-in phases following major overhauls (change
of cylinder liners, pistons, piston rings, cylinder heads,...). They must be carried out by KOHLER authorized Repair Shop.
Job
Interval
NA
N1
100 h
PRODUCT INFORMATION
IO-G-M-00-061e
MAINTENANCE OF NATURAL GAS ENGINE
Job Description
(Operation before starting up the engine)
0 h
- General inspection and set-up of the engine
(Operations after starting up or break-in phase)
- Change oil KOHLER MOTOROIL (oil sump and cooler)
- Change oil filters
- Analyze waste oil
- Clean the oil centrifuge filter and change the paper filter
- Inspection of the gas ramp filter
- Adjustment of rocker arms and valve lifters. Measure valve height
- Check air/fuel ratio
- Adjust air/fuel ratio to full load, if necessary
- Measure the exhaust back-pressure
- Check damper temperature
- Inspect for leaks in all coolant, oil, gas and exhaust gases system
- Check the cleaning of carburetion system and admission (compressor, intercooler
and inlet manifold)
- Inspection and retightening of flanges and clamps, battery terminals, connectors,
flexible couplings, air filter supports, exhaust piping, oil pipes, etc.