Table 1. Configuration of minimum engine protections.
Measure
Oil temperature
Dual cooling circuit engines
Oil temperature
Single cooling circuit engine
Oil level
Oil pressure
Oil pressure
Explosive areas engines
Water temperature
Engines 90/80,90/55 and 90/40
(194/176ºF 194/131ºF y 194/104ºF)
Water temperature
Engines 120/80, 120/55 and 120/40
(248/176ºF 248/131ºF y 248/104ºF)
Water temperature
Water pressure
Engines 120/80, 120/55 and 120/40
(248/176ºF 248/131ºF y 248/104ºF)
Water pressure
Engines 120/80, 120/55 and 120/40
(248/176ºF 248/131ºF y 248/104ºF)
Explosive areas engines
Water pressure
Water pressure
Explosive areas engines
Air Temperature
PRODUCT INFORMATION
IO-G-M-60-002e
Location
Signal type
4-20 mA (0-150ºC)
Crankcase
(32-302ºF)
NC potential-free contact
Crankcase
with the correct oil level
4-20mA (0-10 bar)
Gallery
(0-145 psi)
NC potential-free contact
Before filters
(only V
engines)
Main Circuit
Outlet
4-20 mA (0-150ºC)
(32-302ºF)
Auxiliary
Circuit Inlet
NC potential-free contact
in operation without alarm
Main Circuit
Outlet
4-20mA (0-10 bar)
(0-145 psi)
Discharge
Main Circuit
pump
NC potential-free contact in
operation without alarm
Discharge
Auxiliary
Circuit pump
Discharge
Main Circuit
pump
4-20mA (0-10 bar)
(0-145 psi)
Discharge
Auxiliary
Circuit pump
4-20 mA (0-150ºC)
Engine inlet
(32-302ºF)
INDEX
K
FG/FGLD/SFGLD/SFGM/SFGRD
ENGINES INSTRUMENTATION
Protection value
> 105ºC (221ºF)
> 100ºC (212ºF)
> 107ºC (224,6ºF)
> 104ºC (219,2ºF)
High
Low
< 3,9 bar (56,6 psi)
< 3,6 bar (52,2 psi)
> 6 bar (87 psi)
Does not apply
> 92ºC (197,6ºF)
> 96ºC (204,8ºF)
> 122ºC (251,6ºF)
> 126ºC (258,8ºF)
-
< 2,6 bar (37,7 psi)
< 0.5 bar (7,3 psi)
-
2.9.2
DATE
May 2016
O&M_2.002211.810_A_10_2016
Action
Gradient shutdown
Always
Alarm or warning
Always
Gradient shutdown
Always
Alarm or warning
Always
Alarm or warning
Always
Emergency shutdown
Always
In operation
Alarm or warning
In operation
Emergency shutdown
In operation
Alarm or warning
Alarm or warning
Always
Emergency shutdown
Always
Alarm or warning
Always
Emergency shutdown
Always
Display
Always
Gradient shutdown
Under load
Alarm or warning
Under load
Power correction.
Always
(See IC-G-B-00-001e)
Dep. 3
Active
+ 20 s
+ 20 s
+ 20 s
2/5