The wiring diagram below shows the installation with two starter motors.
The auxiliary start-up relay (4) should be fitted as close as possible to the engine, either in the terminal box or
on the starter motor itself.
The system has a series of batteries to power the electric starter. The standard batteries used by Kohler
to start its engines are LEAD BATTERIES. The battery capacities are the minimum needed for the
maximum current during start-up.
If the batteries are to provide other services apart from engine start-up, the installer should size their capacity to
satisfy the services to be provided. A voltage of 24 V DC has been adopted for the starter motor. The batteries
are 12 V and two are installed in series.
PRODUCT INFORMATION
IT-C-A-55-001e
Fig. 1.2 - Overview of electric start with two starter motors
1
Battery (12 V DC)
2
Master switch
3
Starter motor
4
Auxiliary start-up relay
A
Earth insulation
B
Earth connection
Table 1 - Electrical schematic components