Kohler SFGLD480 Operation & Maintenance Manual page 232

Generator set models 750/1000rezk
Table of Contents

Advertisement

major interventions
Job
Interval
R1
11,200 h
PRODUCT INFORMATION
IO-G-M-00-061e
MAINTENANCE OF NATURAL GAS ENGINE
SFGLD 1800 RPM PRIME
Periodic interventions (Type "R")
Job Description
- Recondition cylinder heads.
- Clean pistons, cylinder liners and cylinder head seating on block
- Check valves driving system: valve lifters, rocker arms, push-rods, roller rocker arms
and cams
- Measure cylinder liners wear
- Clean oil sump
- Check and clean the cooling system. Clean pipe bundles and change gaskets on
heat exchanger and coolers
- Change oil thermostat (only V engine)
- Test thermostats of coolant circuit.
- Clean filters of coolant circuit. Change filter cartridge
- Retighten connections in knocking detection system unit.
- Check-up of electric or pneumatic starting motor.
- Check-up of battery charging alternator
- Change hoses and clamps.
- Check safety valves in intake manifold
- Check and clean the intake circuit, from the air filters outlet to the intercooler (*
- Test control and safety devices: temperature and pressure switches and probes
- Change high voltage wires of the ignition system
- Recondition turbochargers
5.1.9